C-IR-0303M is a module on the CIB bus, which contains 3 AI / DI inputs, 3 relay outputs with a switching contact (2 with a common input and 1 separately connected to the terminal board).
The module is suitable, for example, for supplementing the control of heating circuits - both for common installations in the field of M&R and for the OEM segment - variant addition of heating circuits for CP-2970 / CP-1970 used as a control system for heat pumps and similar devices.
|
Power supply |
|
| Power tolerance |
24 V DC -15% +25% |
| Internal protection |
No |
| Maximum consumption |
60 mA |
| Galvanic separation from internal circuits |
No |
| Cross section of wires to terminals |
2,5 mm2 |
| I/O parameters |
|
|||
| Number of inputs |
3 |
|||
| Input type - Optional SW configuration | Binary, Balanced, PT1000, Ni1000, NTC12k, KTY81-121, Resistance 100kΩ, pulse counter, voltage input 0 ÷ 2V | |||
| Galv. separation of inputs from the CIB |
No |
|||
| Binary input - for without voltage contact [internal voltage / internal resistance] |
(0 .. >1,5kΩ / 1 .. <0,5kΩ) [3,3 V / 2 kΩ] |
|||
| Balanced resistance input |
2 x 1 kΩ (tamper / 0 / 1 / tamper) |
|||
| Pt1000 sensor |
-90 °C ÷ +320 °C |
|||
|
Ni1000 sensor |
-60 °C ÷ +200 °C |
|||
|
NTC12k sensor |
-40 °C ÷ +125 °C |
|||
|
KTY81-121 sensor |
-55 °C ÷ +125°C |
|||
| Resistance input |
0 ÷ 100 kΩ |
|||
| Basic measurement accuracy |
2% |
|||
| Relay outputs |
|
|||
| Number of outputs in the group |
1 (DO3) |
2 (DO1, DO2) | ||
| Contact type | switching 16 A (used relay) | switching 5 A (used relay) | ||
| Galvanic separation from internal circuits |
yes |
|||
| Type of outputs | electromechanical relay, unprotected | |||
| Contact type | Switching NO | |||
| Treatment of inductive load |
external RC element, varistor, diode (DC) |
|||
| Insulation voltage between outputs and internal circuits |
4000 V AC |
|||
|
Insulation voltage between groups |
4000 V AC |
|||

Fig. 1 C-IR-0303M module terminals
English