In order to integrate the control system for skylights, side-hung windows, windows that open to the outside and horizontal pivot windows Schüco TipTronic, you can use the signals of control electronics (BUS-A and BUS-B) for direct control of each window by the Foxtrot system.
Any relay outputs of the system can be used for the control; it is appropriate to use two separate, mutually independent outputs - see the example with the C-OR-0202B module.
Fig. 1. Connecting a Schüco TipTronic window to the C-OR-0202B module
Notes:
-
The total length of the cable between the Foxtrot module and the window should not exceed 30 m.
-
The cable must not lead alongside other cables, especially power cables.
-
It is recommended to use separate relay outputs for the control, so that all control functions enabled by the system can be used (even simultaneous switching on both outputs represents a specific function).
-
The DO1 output opens the window, the DO2 output closes it.