Fire detectors from the EXODUS series, manufactured by TEXECOM, can be used for monitoring areas as a part of fire prevention. The detectors are available in four designs, depending on the type of protected area. All variants have the same mounting base with the terminal block, the same size and design. The detectors are approved for protection in family houses and buildings intended for housing.

Selection of a suitable detector depends on the type of space:

rooms, offices (dust free environment) EXODUS OH/4W

kitchens, garages, boiler rooms EXODUS RR/4W

boiler rooms, operations up to 50 °C EXODUS FT64/4W

boiler rooms, operations up to 80 °C EXODUS FT90/4W

 

The EXODUS OH/4W is a detector with optical detection of smoke and thermo-differential detection of rising temperature;

it detects dense smoke (smoldering fire) or little smoke and a temperature rise from fast flaming fires; it is suitable for fast detection of a normal fire; the resistance to false alarms is higher compared with only optical or ionization detectors, which are not suitable for smoky, dusty and steamy environment (a kitchen, bars, bathrooms).

 

The EXODUS RR/4W works on the principle of thermo-differential detection of temperature rise (rapid increase in temperature), or triggers an alarm when the temperature exceeds 58°C; it is suitable for fast fire detection in smoky or dusty environment, e.g. in bars, attics, and in spaces where the temperature does not exceed 38°C; it is not suitable for environments where the temperature changes rapidly, such as bathrooms or kitchens.

 

The EXODUS FT64/4W works on the principle of fixed temperature heat detectors, and it triggers alarm when the temperature reaches 64 °C; it is suitable for fire detection in a smoky environment, or where temperature changes rapidly, e.g. bathrooms, kitchens and other areas where temperatures exceed 44 °C; it is not suitable for rapid detection of slow burning or smoldering fires or for operating temperatures above 44 °C.

 

The EXODUS FT90/4W operates on the principle of thermo-maximum detection of temperatures above 90 °C; the detector is suitable for environments with temperatures up to 70 °C, e.g. boiler rooms, but it is not suitable for rapid detection of slow burning or smoldering fires.

 

Tab. 1. The basic parameters of the EXODUS fire detectors

Type

EXODUS OH/4W

EXODUS RR/4W

EXODUS FT64/4W

EXODUS FT90/4W

The principle of detection

Dual, optical for smoke and a change of temperature

Detection of temperature rise

Detection of maximum temperature above 64 °C

Detection of maximum temperature above 90 °C

Alarm output

NC, max. 50 mA

Supply voltage

9 ÷ 16 VDC

Consumption

15 mA

Colour

White

Colour differentiation

blue

green

orange

red

Operating temperature

-10 ÷ +55 °C

-10 ÷ +55 °C

-10 ÷ +55 °C

-10 ÷ +80 °C

Assembly

on the ceiling (identical mounting base for all variants)

Dimensions

diameter 107 mm, height 55 mm

The weight

200 g

 

Fig. 1. A picture of the EXODUS detector (the coloured ring determines the exact type).

 


Fig. 2. An example of connecting the EXODUS 4W detector to the C-WG-0503S module

 

Notes:

  1. The example is applicable to all variants of the EXODUS detectors (they have the same mounting base with the terminal block).

  2. Terminals A to F are arranged in a circle around the perimeter of the detector.

  3. Correct installation of the detector is specified in the product operating instructions.

  4. The NC terminal is not used.

  5. A cable with the wire diameter of at least 0.3 mm can be used for the connection, e.g. the SYKFY cable; its length can be up to dozens of meters.