Heating, ventilation 19.03.2020 10:01 19.03.2020 10:01

The module is no longer for sale

The C-VT-0102B module is intended for powering and controlling up to two independent inVENTer ventilation units. The module is powered from the CIB at maximum power of both fans, its consumption is up to 5 W - i.e. the CIB is loaded like with about 5 standard CIB modules.

The module is fitted with an input for an external temperature sensor (indoor temperature, outdoor temperature, etc.).

The InVENTer units are connected directly to the output module wires; the order of the outer terminals (outputs A1 and A2, or B1 and B2) does not matter, only the direction of the fan rotation is reversed, which must be counted with during regulation.

 


Fig. 1. An example of connecting the C-VT-0102B module with two INVENTER units

 

  1. Temperature sensor (input TSa, TSb) - you can use: NTC 12k, NTC thermistors with maximum resistance 160k.

  2. The inVENTer units fans are connected directly in the module outputs, maximum length of supply power wires - 15 m.

  3. The C-VT-0102B module has a maximum power consumption 5 W (with two fans and maximum speed).