The RS-485 serial interface submodule (the MR-0114 type, order no. TXN 101 14) is fitted with a complete circuit of bus termination, terminated at C4 (signal BT +) and C3 (signal BT) terminals, see Fig..1. The termination is connected to the bus by connecting BT+ and TxRx+ terminals, or BT- and TxRx- (for an example, see Fig. 2.5.2.1).
Fig. 1 The connection of the RS-485 interface in the MR-0114 submodule and its termination on the C terminal block.
BT+ positive terminal of the bus termination circuit
BT- negative terminal of the bus termination circuit
GND signal ground (a common terminal) interface
TxRx+ positive interface signal terminal RS-485
TxRx- negative interface signal terminal RS-485
Note:
-
The terminals (signals) with identical marking are interconnected inside the submodule.
-
Terminating bus impedance is implemented with the resistance of 150 Ω.
-
All terminals are galvanically isolated from the other circuits in the system.