The MR-0160 submodule allows the connection of PLC TECOMAT Foxtrot to two CAN networks with data transfer rates of 500, 250, 125, 50, 20 or 10kBd. It can only be used in the CAN, CAS and CAB modes. The CAN line is terminated only for one channel (arbitrary). The second channel must be terminated by externally connected 120 Ω resistor.
Table. 1 Connection of the serial channel C or D connector, when the MR-0160 submodule is fitted.
|
CP-10x4 |
CP-10x6 |
CP-1000 CP-1091 |
Signal |
Type of signal |
Terminals |
C1 |
Cannot be used |
D1 |
+5 V |
power output +5 V |
C2 |
D2 |
GNDS |
signal ground |
||
C3 |
D3 |
BT1– |
– CAN line termination output |
||
C4 |
D4 |
BT1+ |
+ CAN line termination output |
||
C5 |
D5 |
TxRx1– |
channel 1 received and transmitted data (level -) |
||
C6 |
D6 |
TxRx1+ |
channel 1 received and transmitted data (level +) |
||
C8 |
D8 |
TxRx2– |
channel 2 received and transmitted data (level -) |
||
C9 |
D9 |
TxRx2+ |
channel 2 received and transmitted data (level +) |