Foxtrot basic modules 17.03.2020 17:00 17.03.2020 17:00

The MR-0124 submodule provides the conversion of the serial interface TTL signals to the galvanically isolated RS-422 interface. The interface allows a connection of two cooperating devices (point to point).

Every single line (RxD and TxD) must be terminated at the end of the line with 120 Ohm terminating resistors. Galvanic isolation of the serial interface is provided by a built-in converter and no external supply is required. More details concerning the submodule, its internal connection and settings are specified in the documentation TXV 004 03.

 

Table 1 Wiring of the CH2 serial channel connector fitted with the MR-0124 submodule.

 

CP-10x4
CP-10x5

CP-10x6
CP-10x8

CP-1000

CP-1091

Signal

Type of signal

Usage

Terminals

C1

Cannot be used

D1

+5 V

power output +5 V

 

C2

D2

GNDS

signal ground

 

C3

D3

CTS–

input

control signal 1)

C4

D4

CTS+

input

control signal 1)

C5

D5

RxD–

input

data signal

C6

D6

RxD+

input

data signal

C8

D7

TxD–

output

data signal

C9

D8

TxD+

output

data signal

 

D9

 

 

 

1) Using the signal is described in the manual TXV 004 03. The idle signal level corresponds to logical level 1.