The MR-0104 submodule provides the conversion of TTL signals from serial interface to the RS-232 interface, including galvanic isolation. This interface is intended only for interconnection of two participants (point-to-point). It is suitable e.g. for connecting a TECOMAT PLC and PC for short distances (up to 15 m). Galvanic isolation of the serial interface is provided by a built-in converter and no external supply is required. More details concerning the submodule, its internal connection and settings are specified in the documentation TXV 004 03.
Table 1 Wiring of the CH2 serial channel connector fitted with the MR-0104 submodule.
|
CP-10x4 |
CP-10x6 |
CP-1000 CP-1003 CP-1091 |
Signal |
Type of signal |
Usage |
Terminals |
C1 |
- |
D1 |
+ 5 V |
power output |
|
C2 |
D1 |
D2 |
GNDS |
signal ground |
signal ground of the isolated interface |
|
C3 |
D2 |
D3 |
RTS |
output |
control signal 1) |
|
C5 |
D3 |
D5 |
CTS |
input |
control signal 1) |
|
C7 |
D4 |
D7 |
RxD |
input |
data signal |
|
C8 |
D5 |
D8 |
TxD |
output |
data signal |
1) Using the signal is described in the manual TXV 001 06. The idle signal level corresponds to logical level 1.