The following chapters list the basic parameters of connectors and terminal blocks used in the CFox and RFox modules.
Tab. 1. An informative conversion table of wire cross-sections and diameters.
Nominal cross-section |
The wire diameter |
||
Metric |
AWG |
||
Solid wire |
Stranded conductor |
||
mm2 |
mm |
mm |
– |
0.22 |
0.51 |
0.53 |
24 |
0.34 |
0.63 |
0.66 |
22 |
0.5 |
0.9 |
1.1 |
20 |
0.75 |
1.0 |
1.2 |
18 |
1.0 |
1.2 |
1.4 |
- |
1.5 |
1.5 |
1.7 |
16 |
2.5 |
1.9 |
2.2 |
14 |
4.0 |
2.4 |
2.7 |
12 |