Controllers, displays 25.02.2020 12:31 25.02.2020 12:31

Installations with assumed placement of the control system modules in the control panel require the C-IB-1800 module. It should be placed in the main control panel (together with the basic module) or in subordinate distribution boards (in order to optimize the number of cables in the house).

This module can also be used for connecting the ESS detectors, and the AI/DI1 to AI/DI4 inputs can also be used for measuring temperature, or processing pulse inputs from electricity meters, flowmeters, etc. For more information about powering, maximum power consumption, etc., see the article about the C-IB-1800M module.

 


Fig. 1. An example of connecting the push-buttons scanned by the C-IB-1800M module.

Notes:

  1. The cable for push-button controllers, e.g. SYKFY, JY (St) Y, etc., with the length of up to approx. 30 m.

  2. If there are several controllers in one place, you can use for all of them a common multicore cable. The temperature sensor connection can also lead in a common cable (e.g. if there is a multiple frame on the wall with a push-button control and a temperature sensor, all these signals can lead via a common cable to the control panel); in this case, a shielded cable should always be used.

  3. If the cables are long or run in parallel with LV distribution, shielded cables are recommended, as they reduce the risk of false switching due to interference.