CIB modules 29.06.2020 08:50 29.06.2020 08:50

C-IR-0303M is a module on the CIB bus, which contains 3 AI / DI inputs, 3 relay outputs with a switching contact (2 with a common input and 1 separately connected to the terminal board).

The module is suitable, for example, for supplementing the control of heating circuits - both for common installations in the field of M&R and for the OEM segment - variant addition of heating circuits for CP-2970 / CP-1970 used as a control system for heat pumps and similar devices.

 

Power supply

 
Power tolerance

24 V DC -15% +25%

Internal protection

No

Maximum consumption

60 mA

Galvanic separation from internal circuits

No

Cross section of wires to terminals

2,5 mm2

 

I/O parameters

 

Number of inputs

3

Input type - Optional SW configuration Binary, Balanced, PT1000, Ni1000, NTC12k, KTY81-121, Resistance 100kΩ, pulse counter, voltage input 0 ÷ 2V
Galv. separation of inputs from the CIB

No

Binary input - for without voltage contact [internal voltage / internal resistance]

(0 .. >1,5kΩ / 1 .. <0,5kΩ)

[3,3 V / 2 kΩ]

Balanced resistance input

2 x 1 kΩ (tamper / 0 / 1 / tamper)

Pt1000 sensor

-90 °C ÷ +320 °C

Ni1000 sensor

-60 °C ÷ +200 °C

NTC12k sensor

-40 °C ÷ +125 °C

KTY81-121 sensor

-55 °C ÷ +125°C

Resistance input

0 ÷ 100 kΩ

Basic measurement accuracy

2%

Relay outputs

 

Number of outputs in the group

1 (DO3)       

2 (DO1, DO2)
Contact type switching 16 A (used relay) switching 5 A   (used relay)
Galvanic separation from internal circuits

yes

Type of outputs electromechanical relay, unprotected
Contact type Switching NO
Treatment of inductive load

external RC element, varistor, diode (DC) 

Insulation voltage between outputs and internal circuits

4000 V AC

Insulation voltage between groups 

4000 V AC

 

Fig. 1 C-IR-0303M module terminals