The MR-0104 submodule provides the conversion of TTL signals from serial interface to the RS-232 interface, including galvanic isolation. This interface is intended only for interconnection of two participants (point-to-point). It is suitable e.g. for connecting a TECOMAT PLC and PC for short distances (up to 15 m). Galvanic isolation of the serial interface is provided by a built-in converter and no external supply is required. More details concerning the submodule, its internal connection and settings are specified in the documentation TXV 004 03.
Table 1 Wiring of the CH2 serial channel connector fitted with the MR-0104 submodule.
| 
 | CP-10x4 | CP-10x6 | CP-1000 CP-1003 CP-1091 | Signal | Type of signal | Usage | 
| Terminals | C1 | - | D1 | + 5 V | power output | 
 | 
| C2 | D1 | D2 | GNDS | signal ground | signal ground of the isolated interface | |
| C3 | D2 | D3 | RTS | output | control signal 1) | |
| C5 | D3 | D5 | CTS | input | control signal 1) | |
| C7 | D4 | D7 | RxD | input | data signal | |
| C8 | D5 | D8 | TxD | output | data signal | 
1) Using the signal is described in the manual TXV 001 06. The idle signal level corresponds to logical level 1.
 English
 English 
                                    