The JABLOTRON 100 alarm system (JA-JA-101K and 106K control panels) can be integrated via the JA-121T module - a universal bus interface RS-485 of the JABLOTRON 100th system.
The module should be connected to the Foxtrot system via the RS-485 serial interface to the communication channel, e.g. the CH2 channel of the CP-1000 basic module (see the example below) or to an external communication module SC-1101.
The JA-121T module also requires an external supply voltage of 12 V DC, which can be provided either by an external source, e.g. the DR-15-12 (see the example below), or you can utilize the of 12 V DC output level of the PS2-27/60 power supply.
The JA-121T module is mounted on the JABLOTRON 100 bus, which is designed for connecting various parts of the system - detectors, keypads, sirens, etc. It is a four-wire bus with free topology; precise principles of installation, including the connection of the JA-121T module, are described in the JABLOTRON documentation.
The JA-121T module is suppled in an uncovered DPS, and it can be mounted in a flush box.
The basic parameters of the JA-121T module
TBD
The JA-101K control panel is an essential element of the JABLOTRON 100 security system.
It offers flexible setting and facilitates protection of small business spaces, larger houses, offices and firms. The desired setting and the size of the system is programmed using the F-link software.
The JA-101K control panel offers:
– up to 50 wireless or bus zones
– up to 50 user codes
– up to 6 sections
JA-106K is an extended version of the JABLOTRON 100 system control panel.
It offers flexible setting and provides intelligent protection of larger houses, offices and firms. It also offers a flexible solution for protection of residential complexes, office buildings and firms that need a system with many sections. The desired setting and the size of the system are programmed via the F-link software.
The JA-106K control panel offers:
– up to 120 wireless or bus zones
– up to 300 user codes
– up to 15 sections
Fig. 1. An example of connecting the JA-121T module to the CP-1000 basic module