Security and fire alarm detectors, access control 21.02.2020 17:54 21.02.2020 17:54

We recommend the basic variants of the Elite detectors, the TEXECOM and Tecnoalarm manufacturers for outdoor applications of motion detectors (the perimeter protection).

The Elite-EXT-TD-B detector is a PIR scanner with two sensors; the range and sensitivity are adjustable, it has the day/night modes, supplied in white or black version.

The outdoor dual Elite Orbit DT detector is a combined PIR + MW detector with a large range, in an elegant design for wall mounting.

Trired is an outdoor triple PIR detector manufactured by Tecnoalarm, with the curtain characteristics, anti-masking protection and anti-opening and anti-detachment tamper. It features an adjustable detection of masking and range for each beam.

 

Tab. 1. The basic parameters of the Elite and TRIRED outdoor motion detectors

Type

External TD

Elite Orbit DT

TRIRED

Order number

031 32000 (white)
031 32001 (black)

031 32101

031 74600

The principle of detection

mirro technology, two PIR sensors

digital technology PIR+MW

Tripple PIR detector

range

Adjustable 2, 5, 8, 12 m

Adjustable 10, 20, 30 m

30 m

Detection angle

90 °

90 °

 

Rotating optics

180 °

180 °

 

Sensitivity adjustment

2 to 4 pulses (adjustable)

1 to 2 pulses (adjustable)

 

Alarm output

NC, max. 100 mA

2x, NO and NC, max. 50 mA

NC, max. 50 mA

Sabotage contact

NC, max. 100 mA

NC

NC, max. 50 mA

LED indication

yes

yes

 

Temperature comensation

yes

yes

 

Supply voltage

9 ÷ 16 VDC

9 ÷ 15 VDC

10.5 ÷ 14.5 VDC

Consumption

28 mA

15 mA

27 mA

Operating temperature

-35 to + 55 °C

-20 to + 60 °C

-25 to + 65 °C

Operating humidity

max. 95 %

max. 95 %

max. 95 %

Assembly, the height

on the wall, typically 1.0 ÷ 1.4 m

on the wall, typically. 1.5 ÷ 6 m

on the wall, typically. 1.35 ÷ 2.2 m

Dimensions

250 x 86.5 x 87 mm

141 x 165.5 x 109 mm

82 x 400 x 260 mm

The casing colour

White or black

silver

White

The weight

500 g

300 g

1.3 kg

Protection

IP65

IP55

IP55

 

 


Fig. 1. An example of connecting the External TD motion detector to the C-WG-0503S module

 

Notes:

  1. The connection assumes the use of double balanced loop; both the JP7 and JP6 jumpers in the detector must be set to 1 k resistance. (see the general description of double balancing in Chap.8.1.1).

  2. Correct installation of the detectors is specified in the product operating instructions.

  3. A cable with the wire diameter of at least 0.3mm can be used for the connection, e.g. the SYKFY cable; its length can be up to dozens of meters.

 

The Elite Orbit DT and Trired detectors are connected in the same way as e.g. the interior detectors; using double balancing, the external 1 k resistors should be connected to the ALARM and TAMPER outputs