TC800 processor and communication modules 09.01.2025 13:42 09.01.2025 13:42

The SC-8101 module is a system communication module that allows the central unit to be expanded with two additional serial channels that support UNI mode (a general-purpose asynchronous communication channel), PC mode, and PFB mode (for connecting PROFIBUS DP slave stations to a PLC). . 

The TECOMAT PLC central units allow for the connection of up to 6 serial channels on a single TCL3 bus line, i.e., 3 SC-8101 communication modules.
The SC-8101 contains 2 serial channels, each equipped with seperate RS-232 and RS-485 interfaces. 

The module is equipped with two screwless, removable 10-terminal connectors that lock in place when inserted into the module. Each channel has a separate connector; the maximum conductor cross-section is 1.5 mm².

The configuration of an RS-232 or RS-485 interface is made during serial channel configuration in the Mosaic environment (only RS-485 can be used in PFB mode).
Table 1 shows the terminal connections for the SC-8101 module. 

 

Table 1: Signal connections on the module ports

A1

COM1

common for channel 1

A6

COM1

common for channel 1

A2

RTS1

RTS signal

A7

BT1+

+ RS-485 line termination output

A3

CTS1

CTS signal

A8

BT1–

– RS-485 line termination output

A4

TxD1

RS-232 transmit data (Tx)

A9

TxRx1+

transmit and receive data RS-485 (+ level)

A5

RxD1

RS-232 receive data (Rx)

A10

TxRx1–

transmit and receive data RS-485 (- level)

B1

COM2

common for channel 2

B6

COM2

common for channel 2

B2

RTS2

RTS signal

B7

BT2+

+ RS-485 line termination output

B3

CTS2

CTS signal

B8

BT2–

– RS-485 line termination output

B4

TxD2

RS-232 transmit data (Tx)

B9

TxRx2+

transmit and receive data RS-485 (+ level)

B5

RxD2

RS-232 receive data (Rx)

B10

TxRx2–

transmit and receive data RS-485 (- level)

 

Fig. 1: Front view of the SC-8101 module

 

RS-485 Line Termination

RS-485 line termination is performed by connecting the BT+ terminal to TxRx+ and the BT– terminal to TxRx– of the corresponding channel. The RS-485 line must be terminated at each device located at either end of the line. If a device is connected in the middle of the line, termination is not required.