The SC-8101 module is a system communication module that allows the central unit to be expanded with two additional serial channels that support UNI mode (a general-purpose asynchronous communication channel), PC mode, and PFB mode (for connecting PROFIBUS DP slave stations to a PLC). .
The TECOMAT PLC central units allow for the connection of up to 6 serial channels on a single TCL3 bus line, i.e., 3 SC-8101 communication modules.
The SC-8101 contains 2 serial channels, each equipped with seperate RS-232 and RS-485 interfaces.
The module is equipped with two screwless, removable 10-terminal connectors that lock in place when inserted into the module. Each channel has a separate connector; the maximum conductor cross-section is 1.5 mm².
The configuration of an RS-232 or RS-485 interface is made during serial channel configuration in the Mosaic environment (only RS-485 can be used in PFB mode).
Table 1 shows the terminal connections for the SC-8101 module.
Table 1: Signal connections on the module ports
|
A1 |
COM1 |
common for channel 1 |
A6 |
COM1 |
common for channel 1 |
|
A2 |
RTS1 |
RTS signal |
A7 |
BT1+ |
+ RS-485 line termination output |
|
A3 |
CTS1 |
CTS signal |
A8 |
BT1– |
– RS-485 line termination output |
|
A4 |
TxD1 |
RS-232 transmit data (Tx) |
A9 |
TxRx1+ |
transmit and receive data RS-485 (+ level) |
|
A5 |
RxD1 |
RS-232 receive data (Rx) |
A10 |
TxRx1– |
transmit and receive data RS-485 (- level) |
|
B1 |
COM2 |
common for channel 2 |
B6 |
COM2 |
common for channel 2 |
|
B2 |
RTS2 |
RTS signal |
B7 |
BT2+ |
+ RS-485 line termination output |
|
B3 |
CTS2 |
CTS signal |
B8 |
BT2– |
– RS-485 line termination output |
|
B4 |
TxD2 |
RS-232 transmit data (Tx) |
B9 |
TxRx2+ |
transmit and receive data RS-485 (+ level) |
|
B5 |
RxD2 |
RS-232 receive data (Rx) |
B10 |
TxRx2– |
transmit and receive data RS-485 (- level) |

Fig. 1: Front view of the SC-8101 module
RS-485 Line Termination
RS-485 line termination is performed by connecting the BT+ terminal to TxRx+ and the BT– terminal to TxRx– of the corresponding channel. The RS-485 line must be terminated at each device located at either end of the line. If a device is connected in the middle of the line, termination is not required.