TC800 frames, power supplies and cables 24.09.2024 09:06 24.09.2024 09:06

The RM-895x series system bus for the TC800 system is designed for mounting on a 35 mm DIN rail with a depth of 15 mm. 

The RM-895x series features TCL3 bus termination via KB-8961 end pieces, that are mounted on both ends of the system bus, see Fig. 1. The KB-8961 terminator end pieces are standard components included with the RM-895x series system bus and must be installed as described. 

For example, RM-8955.02, order no. TXN 189 55.02, is a set of the RM-8955 system bus with 2 KB-8961 terminator end pieces. The RM-895x system bus cannot be ordered separately. The KB-8961 terminator can be ordered separately, e.g., to replace a damaged part, under order number TXN 189 61.

Fig. 1 RM-8955 system bus with KB-8961 terminators

Notes:

  1. The system bus (RM-8955) snaps onto a standard 35 mm DIN rail with a depth of 15 mm, with the red arrows pointing upward as shown in the figure. The system bus has a relatively tight fit in the DIN rail and must be pressed firmly into place; care must be taken not to damage the bus itself (the gold-plated conductive strips).
  2. The KB-8961 end piece is snapped onto both the left and right ends of the system bus, also with the red arrows pointing upward
  3. There is a gap of approx. 5 mm in height and 9 mm in width between the system bus and the DIN rail for the screw heads securing the DIN rail—see the bottom left of fig. 1.
  4. It is recommended to cover the unused sections of the bus with the 8 blanking plugs supplied in the BS-C028 kit.

 

 

KB-8961, TC800 bus terminator.

This is required for proper termination of the TCL3 bus in the TC800 system when using system buses that do not have built-in termination.

These terminators are now required for the RM-895x series of system buses, which are designed for 15 mm deep DIN rails.

The older RM-894x series has internal termination, and KB-8961 modules MUST NOT be installed on these system buses!

Fig. 2 Terminator end piece KB-8961