Controllers, displays 28.11.2025 09:40 28.11.2025 09:40

The ID-104, order number TXN 055 23, is a 10-inch color graphic control panel with a touchscreen. It is designed to work with the TECOMAT TC800 and Foxtrot controllers to display custom made web pages. User screens are created in the Mosaic programming environment using the WebMaker tool and are identical to the pages available on Tecomat via a web server using a ordinary web browser.

The panel features a backlit 10-inch capacitive touchscreen TFT LCD display with a 16:10 aspect ratio and a resolution of 1920x1200 pixels. Power is supplied by an external 24 V DC power source. Communication between the controller and the ID-104 panel takes place via a 100Base-TX Ethernet interface. The panel is designed for wall mounting in a standard 68 mm installation box or for mounting on a control panel door using a sheet metal bracket (TXN 055 23.93) and double-sided adhesive film (TXN 055 23.92), which can be ordered separately.

Order numbers for the ID-104 and optional accessories:

TXN 055 23 Complete ID-104 control panel kit for installation in a junction box (consists of the panel, base, and mounting screws).

TXN 055 23.92 double-sided adhesive backing for 10" (adhesive backing for mounting the ID-104 panel into an opening in an enclosure, e.g., a control panel)

TXN 055 23.93 10" metal display bracket (bracket for mounting the complete ID-104 panel into an opening in an enclosure, e.g., a control panel)

 

A bracket shared with the 7" display can also be used:

TXN 055 22.95 7" wall-mount bracket (bracket for mounting the ID-74 panel on a drywall)

 

Panel Mounting

The panel can be mounted on a thin sheet, such as a metal or plastic cabinet door. For mounting, you can order a double-sided adhesive pad and a metal bracket. For mounting on a 1 mm thick sheet metal cover, M4x16 screws are optimal; when using a flat washer, the maximum tightening torque is 1.2 Nm.

Fig. 1 Installation of the ID-104 in a thin wall (here, a 1-mm-thick wall)

The hole in the wall must be cut out with moderate precision, as the self-adhesive film (shown in black in the figure) is thin. Figure 2 shows the required dimensions of the hole and the placement of the ID-104 panel relative to the hole.

Fig. 2 Dimensions of the mounting hole for the ID-104 in a thin wall (rámeček = frame, viditelná plocha displeje = visible screen area, otvor v panelu = panel opening)

The position of the adhesive film (highlighted in blue) is shown in Fig. 3. The mounting screws on the snap-on bracket are visible on the sides.

Fig. 3: Placement of the adhesive film and metal bracket (double-sided adhesive tape shown in black)

The metal bracket rests against the rear wall of the housingboth at the top and bottom into which it is installed. Double-sided adhesive tape is applied to both surfaces of the metal bracket.

Fig. 4: Side view showing the placement of the adhesive film and the metal bracket, with the adhesive labels indicated

 

 

Mounting on a brick wall

The ID-104 panel is primarily designed for wall mounting on a standard junction box, such as the KU-68. A base plate, which includes an Ethernet connector and 24 V power terminals, is screwed onto the installation box. The panel itself its main component is then snapped onto the secured base plate. This completes the installation.

Fig. 5: Rear view of the ID-104 in the mounting configuration for an electrical box (in this case, the M4 screws shown are not used for mounting)

Notes:

  1. The dark grey area represents the base, which is screwed onto the junction box.
  2. Ensure correct orientation during installation as shown in the figure (Ethernet connector facing down).
  3. The base features a terminal block to which the 24 VDC power supply is connected; the terminals are labeled in the figure (negative terminal GND, positive terminal VDC).
  4. The panel itself hooks onto the top of the base (be careful of the interconnecting connector), then the bottom tabs are folded down and snapped into place.
  5. To remove the panel, follow the steps in reverse—pull to release the lower tabs, then tilt the panel out.
  6. The lower tabs also allow the panel to be secured with small screws to prevent it from being removed from the wall; the screws are included and should be screwed in tightly along the bottom of the wall from the underside; a TORX T6 screwdriver is required.

 

 

The panel itself can be secured to the base after snapping it into place using the two small screws included in the package.

The screws are inserted from the underside of the panel and require a TORX T6 screwdriver.

 

 

Mounting on a drywall, wood, etc.

For wall mounting where there is no junction box, you can order a mounting bracket (TXN 055 22.95), which is screwed into the wall; the base is then screwed into the bracket, and the installation proceeds as described for brick wall mounting.

Fig. 7 Illustration of the ID-74 panel with a wall mounting bracket (the mounting bracket is shown in dark gray) — the ID-104 uses the same design

 

Dimensions of the ID-104 Operator Panel

Fig. 8 Dimensions of the ID-104 Operator Panel (when mounted on a brick wall using a standard electrical box)

Fig. 9 Dimensions of the ID-104 Operator Panel (when mounted on a wall using the TXN 055 23.93 sheet metal bracket)

 

Specifications

Power connection

Push-in spring terminal blocks
max.1,5 mm2 

IP rating

IP20

Input voltage

24 ÷ 48 V DC

Internal protection

No

Power consumption

7,2 W Max

Maximum weight

530 g

Dimensions

240 x 160 x 20 mm

Product standards

EN 60730

 

 

Operating Specifications
Operating Temperature Range

0 °C to + 40 °C

Storage Temperature Range

-20 °C to + 70 °C

Operating/Storage Humidity

5 % až 80 % RH, no condensation

Operating position

Vertical

Txpe of operation

Permanent

 

Display Specifications

Display

color TFT IPS
16:10 LED 256k

Diagonal Size

10”

Resolution

1920 x 1200

Touch screen

capacitive multitouch