Binary modules 09.02.2020 14:45 15.02.2020 10:18

The OR-0424 module is equipped with 16 relay outputs with switching contacts. The module is equipped with a fixed terminal block with spring contacts. It is an external output module intended for connection to the output binary modules of the control system (eg connection to the OS-7410, OS-7411 and IS-7510 modules of the TC700 system). Each output is indicated by a light-emitting diode. The output contacts are protected by an RC member.

The power consumption of the module is max. 5.5 W and it is necessary (to calculate the consumption from the 24 V DC source) to add the power consumption of the output circuits of the connected control module (eg the power consumption of the output circuits of the OS-7411 module is max. 0.6 W for one connected external module (16 outputs)). For the given example ½ OS-7411 + OR-0424, the power consumption from the 24 V DC source is 6.1 W.

The module is equipped with fixed terminal blocks with spring contacts and a removable R connector for connecting the control system (in the case of using a shielded connection cable to the control system, the shield terminal is connected to the SHIELD faston connector). The connection of the connector is shown in Fig. 11.3.7.1.

Fig. 11.3.7.1 Connection of the OS-0424 module connector

 

COMx common terminal output 

DOx output terminal output x

+ 24 V positive terminal for connecting the power supply of the internal circuits of the connected control system module (eg OS-7411)

0 V negative terminal for connecting the power supply of the internal circuits

of the connected control system module (eg OS-7411)

terminal for connection to the main protective ground of the switchboard (conductor with a cross-section of at least 2.5 mm2). Required for the module cable protection and shielding function.



 

EXAMPLE OF MODULE CONNECTION

 

Fig.11.3.7.2 Example of OR-0424 module connection


 

 

Max. DC contact load