Binary modules 09.02.2020 14:44 15.02.2020 10:18

The OR-0422 module is equipped with 8 relay outputs with changeover contacts. The module is equipped with a fixed terminal block with spring contacts. It is an external output module intended for connection to the output binary modules of the control system (eg connection to the OS-7410, OS-7411 and IS-7510 modules of the TC700 system). Each output is indicated by a light-emitting diode. The output switching contacts are protected by a varistor.

The power consumption of the module is max. 3 W and it is necessary (to calculate the consumption from the 24 V DC source) to add the power consumption of the output circuits of the connected control module (eg the power consumption of the output circuits of the OS-7411 module is max. 0.6 W for one connected external module ( 16 outputs)). For the given example ½ OS-7411 + OR-0422, the power consumption from the 24 V DC source is 3.6 W.

The module is equipped with fixed terminal blocks with spring contacts and a removable R connector for connecting the control system (in case of using a shielded connection cable to the control system, the shield terminal is connected to the SHIELD faston connector) and a removable S connector for connecting the second eight outputs (external module with 8 outputs ). The connection of the connector is shown in Fig. 11.3.6.1.

Fig. 11.3.6.1 Connection of the OR-0422 module connector

 

DOx changeover contact of output x

+ 24 V  positive terminal for connecting the power supply of the internal circuits of the connected control system module (eg OS-7411)

0 V  negative terminal for connecting the power supply of internal circuits

connected control system module (eg OS-7411)

terminal for connection to the main protective ground of the switchboard (conductor with a cross-section of at least 2.5 mm2). Required for the module cable protection and shielding function.



 

EXAMPLE OF MODULE CONNECTION


 

 

Fig.11.3.6.2 Example of OR-0422 module connection