Inputs and Outputs
The CP-2061 controller contains the following built-in inputs and outputs:
Inputs
-
4× universal inputs DI0–DI3
Each input can be configured as:-
a binary input (10 V DC or potential-free contact),
-
analog input (range 0–10 V / 0–2 V, 12-bit ADC),
-
input for a passive resistance sensor (e.g., Pt1000, Ni1000, NTC),
- counter input (cannot be combined with analog mode).
-
Outputs
-
4× relay outputs DO0–DO3
-
max. 250 V / 3 A AC or DC,
-
galvanically isolated,
-
organized into 2 groups (DO0+DO1 and DO2+DO3) with a single common terminal.
-
-
3× transistor outputs PWM0–PWM2
-
24 V DC, max. 0.5 A continuous (MOSFET, low-side),
-
capable of operating in PWM mode (frequency and duty cycle configurable in the application),
-
outputs are not galvanically isolated,
-
share terminals with analog outputs (AO0–AO2).
-
-
3× analog outputs AO0–AO2
-
voltage outputs 0–10 V, 12-bit DAC,
-
max. output current 10 mA,
-
activated by switching solder jumpers instead of PWM outputs (separately for each).
-
Communication Interfaces
-
1× 10/100 Mb Ethernet (RJ-45)
-
2× serial channels (RS-485, without galvanic isolation)
-
1× USB host (Type A)
-
NFC memory (internal); see example of use in this article
-
1× CIB (Common Installation Bus) line for CFox modules (max. 32 modules, internal power supply 400 mA)
Optional (depending on module variant):
-
internal WiFi interface (WLAN1),
-
external WiFi via USB (WLAN2 – see documentation for supported adapters).
Power Supply and Mechanical Specifications
-
Supply voltage: 24 V DC ±25% (SELV)
-
Maximum power consumption: 10 W
-
Width: 4M (70 mm), Height: 90 mm, Depth: 58 mm
-
Mounting: on a 35 mm DIN rail
-
Terminals: removable, max. wire cross-section: 2.5 mm²
Central Unit
-
J series, Cortex-A5 500 MHz processor (1 core)
-
Memory for user program: 2 MB
-
Memory for variables: 512 kB (of which 48 kB is RETAIN)
-
Integrated RTC with capacitive backup (approx. 500 h)
-
File system: 128 MB internal disk, USB Flash and microSD support
-
Integrated web server and data logger
-
Support for program changes during operation (online editing)
-
Development environment: Mosaic version 2024.1 or later

Fig. 1: Basic wiring diagram of the CP-2061 ("El. ohřívač" = electric heater)