The C-JC-0006M module is equipped with6 outputs designed for standard blinds control – i.e. the so-called three-point-control: opening-idle-closing. The module can also be used for three-point valve control, etc. The module is internally fitted with 6x2 relays with a fixed connection (including the mechanical blocking of simultaneous switching of both outputs) for blinds control, terminated on the module connectors. Continuous current in each output is 3 A, see more detailed information on the relays used). The module is in a 4M box on a DIN rail. There are LED indicators on the front panel (indicating the movement up/down) and push-buttons, which allow manual control of shutters if there is a communication breakdown; if it is allowed by the configuration, a switchover to manual mode is also possible during normal operation of the system.
The module is suitable for switching inductive loads, the type of blinds motors; depending on the load it is recommended to supplement the system with protection varistors (not needed for ordinary blinds motors).
The module can be powered directly from the CIB (its power input limits the number of modules on one branch of the bus), or it can be powered from a separate 24 VDC supply (which can be used for multiple modules placed immediately next to each other); then the CIB bus is not loaded.
If you connect an external 24 V supply to the A5 and A6 terminals, the module power supply will be automatically switched to the supply source connected to these terminals. To switch the power supply, a higher voltage than 19.2 V must be brought to the A5 terminal.
External 24 VDC power supply (the A5, A6 terminal) |
19.2 ÷ 30 VDC |
Maximum consumption from the 24 VDC external power supply connected to the A5 or A6 terminal. |
63 mA |
Isolation voltage:
between individual connectors is 4,000 VAC (safe isolation of circuits),
between the outputs DO1 and DO2 the isolation voltage is 1,000 VAC.
between the outputs DO3 and DO4 the isolation voltage is 1,000 VAC.
between the outputs DO5 and DO6 the isolation voltage is 1,000 VAC
The module is equipped with a relay with continuous current 3A and terminal blocks with a maximum wire cross-section 2.5 mm.2
Fig. 1 The basic connection of the C-JC-0006M module