Water pressure 01.03.2020 09:44 04.03.2020 17:54

Monitoring the pressure of water in the heating circuit (monitoring any leakages) can be done using a pressure switch with a contact output, e.g. the Presostat KPI 35 (order number 060-121766) DANFOSS, or the 61214 ZPA EKOREG.

The Presostat KPI 35 enables setting the pressure range, within which the unit sends a signal, i.e. a differential pressure, when the contact system switches the contact on and off. The output changeover contact should be connected to the binary system input, e.g. the C-AM-0600I module.

 

Pressure switch KPI 35

The setting range

[bar]

-0.2 ÷ 8

The differential range

[bar]

0.4 ÷ 1.5

Connection

 

G¼A

Protection

 

IP 33

The material of the contacts

 

Ag

Ambient temperature

°C

– 40 to +65

The temperature of the medium

°C

– 40 to +100

Medium

 

air, oil, clean water

The cable gland

mm

6 – 14

 


Fig. 1. Connecting the KPI 35 pressure switch to the C-AM-0600I module