Tab. 1 Terminating of the CH2,CH4 and DO0-1 communication channels for CP-10x6, CP-10x8
Terminal block D |
Terminal |
MR-0105 |
MR-0106 |
MR-0115 |
|||
D1 |
GNDS |
GNDS |
GNDS |
||||
D2 |
TxD4 |
CH3 RS-232 |
TxRx4– |
CH3 RS-485 |
TxRx4– |
CH3 RS-485 |
|
D3 |
RxD4 |
TxRx4+ |
TxRx4+ |
||||
D4 |
RxD2 |
CH2 RS-232 |
RxD2 |
CH2 RS-232 |
TxRx2+ |
CH2 RS-485 |
|
D5 |
TxD2 |
TxD2 |
TxRx2– |
||||
D6 |
- |
||||||
D7 |
COM1 |
||||||
D8 |
DO0 |
||||||
D9 |
DO1 |
Notes:
-
The D6 terminal must remain unconnected, as it provides safe galvanic isolation of communication channel circuits from the DO0 and DO1 binary outputs.