These relays are fitted in e.g. the C-OR-0011M-800, C-LC-0202B, C-HM-1121M, R-HM-1121M peripheral modules, and others (see the information on the individual modules).
Tab. 1. The parameters of the actual relay contact (each specific module can have different values!):
Nominal current |
16 A at 230 VAC or 24 VDC |
|
Maximum transmitted current |
16 A |
|
Maximum switching inrush current (incandescent bulbs) (fluorescent lamps) |
165A , maximum 20 ms 800 A, maximum 200 μs |
|
Maximum switching power |
Resistance load, incandescent bulbs, halogenous 230 V bulbs |
3,680 W |
Fluorescent lamps with an electronic ballast |
1,000 VA |
|
Fluorescent lamps with a maximum 64 µF compensation |
500 VA |
|
Mechanical lifetime |
Minimum 5,000,000 operations |
|
Electrical lifetime (at 16 A, 230 VAC, cosφ = 1) |
Minimum 100,000 operations |
|
Electrical lifetime (1.200 W incandescent bulbs) |
Minimum 6,000 operations |
|
Electrical lifetime (620 W discharge lamps - standard ballast) |
Minimum 6,000 operations |
|
Switching time |
Maximum 10 ms |
|
Opening duration |
Maximum 5 ms |
|
Minimum recommended switching voltage, current |
5 VDC, 100 mA |
|
Material of the contact |
W (fore-contact) + AgSnO2 |
The contact loading characteristics: