These relays are fitted in e.g. the Foxtrot basic modules (CP-1005, CP1006, etc.), the peripheral modules (C-HM-0308M, C-IR-0202S) and others (see information on the individual modules).
The parameters of the actual relay contact (each specific module can have different values!):
Maximum switching current | 5 A at 230 VAC |
3 A at 30 VDC | |
Mechanical lifetime | Minimum 5,000,000 operations |
Electrical lifetime (at 5A, 230VAC) | Minimum 100,000 operations |
Electrical lifetime for DC13 inductive load | Minimum 100,000 operations |
Electrical lifetime for AC15 inductive load | Minimum 100,000 operations |
Switching time | Maximum 10 ms |
Opening duration | Maximum 10 ms |
Frequency of switching with nominal load | Maximum 20 operations/min |
Minimum recommended switching voltage, current | 5 VDC, 10 mA |
The contact loading characteristics: