The C-AM-0600I is a universal input module designed to measure temperature, pulse inputs, flowmeters and water meters, gas meters and electricity meters with the S0 output (class A, measuring current of approximately 10 mA). At the same time the module allows connecting a flooding sensor (condensation), or a dewing sensor and a flowmeter with an integrated thermometer AV23. For an overview of the signals measured, see the table below.
The module is housed in a wall-mounted plastic box with a higher protection, with 7 soft self-sealing cable glands. For an easy assembly, the module is equipped with side fitting for screwing or tightening with cable ties. The lid of the box can be fixed into place by snapping.
An overview of the measuring sensors, pulse and analogue signals:
The measuring sensors and ranges |
AI1 |
AI2 |
AI3 |
AI4 |
AI5 |
AI6 |
Measuring temperature: Pt1000, Ni1000, NTC 12k, NTC up to 200 kΩ |
● |
● |
● |
● |
● |
|
Standard signals: 0÷20 mA, 4÷20 mA, 0÷1 V, 0÷2 V, 0÷10 V |
● |
● |
● |
● |
● |
|
● |
● |
● |
● |
● |
|
|
● |
● |
● |
● |
|
|
|
|
|
|
|
● |
|
|
|
|
|
|
● |
|
|
|
|
|
|
● |
|
|
Resistance up to 450 kΩ |
|
|
|
|
● |
|
|
|
|
|
|
● |
Basic technical data:
Level of protection |
IP 55 (ČSN EN 60529) |
Ambient temperature |
-20 ÷ +70 ºC |
Material |
cap: PP-C, grey |
|
Box: PP, TPE glands |
Dimensions: |
85 x 85 x 37 mm (with no fitting) |
Clamp |
self-sealing, the cable diameter 2 ÷ 14 mm |
Terminal block |
the push-In type, wire cross-section maximum 1 mm² |
Fig. 1. The dimensions of the C-AM-0600I module
Notes:
-
On each side of the module there are always three self-sealing glands. Before installing the cable, simply make a hole in the box and gently push the cable in (see the main axes of the glands in the following figure).
-
Mount the box on the wall using the side fittings. The box can also be mounted using cable ties, for which the side fitting have openings to put the ties through.
-
The cap can be opened using a screw driver. There are grooves visible on the side of the box for the screwdriver; if you twist it, the cap opens.
-
The box is made of flexible material. Rough handling, twisting or bending the box may damage the module internal electronics.
Fig. 2. Layout of the terminals in the C-AM-0600I module