The C-WS-0400R-iGlass control units are interior touch control units from the iGlass design series. A coherent group of control units includes variants with 1-6 backlit buttons, a circular sensor, or sometimes with a two-digit display (for see specific variants see the Teco catalogue). The control units are also equipped with an acoustic output and an integrated proximity sensor. All the design variants of the module also contain 2 universal AI/DI inputs. Each of the universal inputs can be used separately either in the function of a binary dry input, or as an analogue input for connecting a resistive temperature sensor.
The module is mechanically adapted for mounting on a standard flush box with 60 mm spacing between the fixing screws. The terminal block for connecting the CIB bus and external AI/DI is on rear side of the module.
There are two basic mechanical versions of the control units: with an 80 x 80 mm front glass (the standard controller shape), or 80 x 120 mm.
The 80 x 80 mm front glass is rectangular, the glass is black with a blue tinge. The variants:
1- push-button, order number TXN 133 72.01
2- push-buttons, order number TXN 133 72.02
4- push-buttons, order number TXN 133 72.04
a dimmer (a circular control unit) order number TXN 133 72.05
4- push-buttons with a display, order number TXN 133 72.07
a 230 V socket, order number TXN 133 72.09
Fig. 1. The placement of the terminal block and the dimensions of the control units C-WS-0x00R-iGlass, the version 80 x 80 mm
Notes:
-
The temperature sensor can be the Pt1000, NI1000, NTC 12k or any other NTC with a resistance up to 100 kΩ; the feeder cable length can be up to dozens of meters - a typical use is a floor sensor, the cable used e.g. SYKFY or similar, with at least 1x2 wires with 0.5 mm diameter.
-
The module is designed as a standard installation element to be mounted on the flush box (KU68).
-
The CIB bus and both universal inputs DI/AI1 and DI/AI2 are terminated on the terminal block in the rear part of the module.
-
Part 2 is a supporting frame on the installation box, into which the actual body of the controller - part 1 (the upper part with a glass front) is not indicated in the picture.
Fig. 2. The dimensions of the control units (the depth) C-WS-0x00R-iGlass, the version 80 x 80 mm
The 80 x 120 mm front glass is rectangular, the glass is black with a blue tinge. The variants:
6 push-buttons order no. TXN 133 72.16
4-push-buttons with a display order no. TXN 133 72.17
a 230 V socket, order number TXN 133 72.19
Fig. 3. The placement of the terminal block and the dimensions of the control units C-WS-0x00R-iGlass, the version 80 x 120 mm
Notes:
-
The temperature sensor can be the Pt1000, NI1000, NTC 12k or any other NTC with a resistance up to 100 kΩ; the feeder cable length can be up to dozens of meters - a typical use is a floor sensor, the cable used e.g. SYKFY or similar, with at least 1x2 wires with 0.5 mm diameter.
-
The module is designed as a standard installation element to be mounted on a rectangular flush box.
-
The CIB bus and both universal inputs DI/AI1 and DI/AI2 are terminated on the terminal block in the rear part of the module.
Fig. 4. The C-WS-0x00R-iGlass control unit, the version 80 x 120 mm.
Notes:
-
Component 2 is the supporting frame in the flush box, into which the body of the control unit (component 1) is gently pressed. The top part with the glass is not shown in the Fig.
Basic parameters of the DI/AI1 and DI/AI2 inputs
The input type (connected sensor) |
The range of measured values |
PT1000 |
-90 °C ÷ +320 °C |
Ni1000 |
-60 °C ÷ +200 °C |
NTC 12k |
-40 °C ÷ +125 °C |
KTY81-121 |
-55 °C ÷ +125 °C |
The range of measuring resistance |
0 ÷ 100 kΩ |
The voltage range |
0 ÷ 2 V |
Binary input |
Log. 0 >1.5 kΩ / log 1 <0.5 kΩ |
The loop resistance 2x 1k1 |
Touch sensors
Capacitive push-buttons |
1 ÷ 6 (according to the type of control unit) |
Circular touch sensor |
1 |
Proximity sensor |
1 (sensitivity on approx. 2 cm) |
A seven-segment display |
2 digits, 2 decimal points |
Basic parameters of the module
Dimensions |
80 x 80 x 50 mm or 120 x 80 x 50 mm |
Operating temperature |
-10 ÷ +55 °C |
Storage temperature |
-25 ÷ +70 °C |
Connecting the screw-type terminal |
Cross-section of wires max. 1.5 mm2 |